Schneider Electric TM3AI2HG Analog input module, Modicon TM3, 2 inputs high resolution (spring) 24 VDC
Main
Range of product Modicon TM3
Product or component type Analog input module
Range compatibility Modicon M221
Modicon M241
Modicon M251
Modicon M262
Analogue input number 2
Analogue input type Current 4...20 mA
current 0...20 mA
voltage 0...10 V
voltage - 10...10 V
Complementary
Analogue input resolution 16 bits
15 bits + sign
Permissible continuous overload 13 V, analogue input type: voltage
40 mA, analogue input type: current
Input impedance <= 50 Ohm current
>= 1 MOhm voltage
LSB value 2.44 mV 0...10 Vvoltage
4.88 mV - 10...10 Vvoltage
4.88 µA 0...20 mAcurrent
3.91 µA 4...20 mAcurrent
Conversion time 1 ms + 1 ms per channel + 1 controller cycle time
Sampling duration 1 ms
Absolute accuracy error +/- 0.1 % of full scale at 25 °C
+/- 1 % of full scale
temperature drift +/- 0.006 %FS/°C
Repeat accuracy +/-0.5 %FS
Non-linearity +/- 0.01 %FS
Cross talk <= 1 LSB
[Us] rated supply voltage 24 V DC
Supply voltage limits 20.4…28.8 V
Type of cable Twisted shielded pairs cable <30 m for input circuit
Current consumption 30 mA at 5 V DC via bus connector no load
40 mA at 5 V DC via bus connector full load
25 mA at 24 V DC via external supply
Local signalling 1 LED (green) for PWR
Electrical connection 11 x 2.5 mm² removable spring terminal block with pitch 5.08 mm adjustment for inputs and supply
Insulation Between input and supply at 1500 V AC
Between input and internal logic at 500 V AC
Marking CE
Surge withstand 1 kV power supply common mode conforming to EN/IEC 61000-4-5
0.5 kV power supply differential mode conforming to EN/IEC 61000-4-5
1 kV input common mode conforming to EN/IEC 61000-4-5
Mounting support Top hat type TH35-15 rail conforming to IEC 60715
Top hat type TH35-7.5 rail conforming to IEC 60715
plate or panel with fixing kit
Height 90 mm
Depth 70 mm
Width 23.6 mm
Net weight 0.1 kg
Environment
Standards EN/IEC 61131-2
EN/IEC 61010-2-201
Resistance to electrostatic discharge 8 kV in air conforming to EN/IEC 61000-4-2
4 kV on contact conforming to EN/IEC 61000-4-2
Resistance to electromagnetic fields 10 V/m 80 MHz...1 GHz conforming to EN/IEC 61000-4-3
3 V/m 1.4 GHz...2 GHz conforming to EN/IEC 61000-4-3
1 V/m 2 GHz...3 GHz conforming to EN/IEC 61000-4-3
Resistance to magnetic fields 30 A/m conforming to EN/IEC 61000-4-8
Resistance to fast transients 1 kV (I/O) conforming to EN/IEC 61000-4-4
Resistance to conducted disturbances 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6
3 V spot frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to Marine specification (LR, ABS, DNV, GL)
Electromagnetic emission Radiated emissions - test level: 40 dBμV/m QP class A ( 10 m) at 30…230 MHz conforming to EN/IEC 55011
Radiated emissions - test level: 47 dBμV/m QP class A ( 10 m) at 230…1000 MHz conforming to EN/IEC 55011
Immunity to microbreaks 10 ms
Ambient air temperature for operation -10…55 °C horizontal installation
-10…35 °C vertical installation
Ambient air temperature for storage -25…70 °C
Relative humidity 10…95 %, without condensation (in operation)
10…95 %, without condensation (in storage)
IP degree of protection IP20
Pollution degree 2
Operating altitude 0...2000 m
Storage altitude 0…3000 m
Vibration resistance 3.5 mm at 5…8.4 Hz on DIN rail
3 gn at 8.4…150 Hz on DIN rail
Shock resistance 15 gn for 11 ms
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 7.5 cm
Package 1 Width 10.5 cm
Package 1 Length 12.5 cm
Package 1 Weight 200.0 g
Unit Type of Package 2 S02
Number of Units in Package 2 9
Package 2 Height 15.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 2.246 kg
Similar model numbers:
TM3AI2H
TM3AI2HG
TM3AI4
TM3AI4G
TM3AI8
TM3AI8G
TM3AM6
TM3AM6G
TM3AQ2
TM3AQ2G
TM3AQ4
TM3AQ4G
TM3TI4
TM3TI4G
TM3TI8T
TM3TI8TG
TM3TM3
TM3TM3G
TM3TI4D
TM3TI4DG