Schneider Electric BMXCPS3522S redundant power supply module X80 - 125 V DC - Safety
Main
Range of product Modicon X80
Product or component type Power supply module
backplane compatibility All backplane
advanced diagnostics available via network Redundancy information
Redundancy test
Remaining lifetime
Temperature sensing
Uptime duration
Primary voltage 125 V
Supply circuit type DC
Secondary power 18 W 3.3 V DC at -25…60 °C I/O module logic power supply
40 W 24 V DC at -25…60 °C I/O module power supply and processor if 3.3 V not loaded
Complementary
Primary voltage limit 100...150 V
Input current 600 A 125 V
Inrush current 60 A 125 V
I²t on activation 2.5 A².s 125 V
It on activation 0.09 A.s 125 V
MTBF reliability 871500 H
Protection type Internal fuse not accessible for primary circuit
Overload protection for secondary circuit
Overvoltage protection for secondary circuit
Short-circuit protection for secondary circuit
Current at secondary voltage 1.67 A 24 V DC I/O module logic power supply
5 A 3.3 V DC I/O module power supply and processor
Maximum power dissipation in W 8.5 W
Status LED 1 LED (green) presence of voltages (OK)
1 LED (green) redundancy OK
1 LED (green) power supply status
Control type RESET push-button cold restart
Electrical connection 1 connector 2 pin(s)alarm relay
1 connector 5 pin(s)line supply, protective earth
Insulation resistance >= 100 MOhm primary/ground
>= 100 MOhm primary/secondary
Net weight 0.64 kg
Environment
Immunity to microbreaks 1 ms
Dielectric strength 1500 V primary/secondary I/O module logic power supply
1500 V primary/secondary I/O module power supply and processor
2300 V primary/secondary sensor power supply
1500 V primary/ground
Vibration resistance 3 gn
Shock resistance 15 gn
IP degree of protection IP20
Directives 2014/30/EU - electromagnetic compatibility
2006/42/EC - machinery
2014/34/EU - ATEX directive
Product certifications CE
UL
CSA
RCM
EAC
Merchant Navy
ATEX zone 2/22
IECEx zone 2/22
TÜV
Standards EN/IEC 61131-2
EN/IEC 61010-2-201
UL 61010-2-201
CSA C22.2 No 61010-2-201
IACS E10
EN/IEC 61000-6-5, interface type 1 and type 2
EN/IEC 61850-3, location G
EN/IEC 60079-0
Environmental characteristic Hazardous location class I division 2
Gas resistant class Gx conforming to ISA S71.04
Gas resistant class 3C4 conforming to IEC 60721-3-3
Dust resistant class 3S4 conforming to IEC 60721-3-3
Sand resistant class 3S4 conforming to IEC 60721-3-3
Salt resistant level 2 conforming to IEC 68252
Mold growth resistant class 3B2 conforming to IEC 60721-3-3
Fungal spore resistant class 3B2 conforming to IEC 60721-3-3
Ambient air temperature for storage -40…85 °C
ambient air temperature for operation -25…60 °C
Relative humidity 5…95 % at 55 °C without condensation
Protective treatment Conformal coating
Operating altitude 0...2000 m
2000...5000 m with derating factor
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 9.0 cm
Package 1 Width 18.0 cm
Package 1 Length 25.0 cm
Package 1 Weight 628.0 g
Unit Type of Package 2 S03
Number of Units in Package 2 6
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 4.4 kg
Similar model numbers:
BMXCPS4002S
BMXCPS3522
BMXCPS4022
BMXCPS3522H
BMXCPS4022H
BMXCPS3522S
BMXCPS4022S
BMXXTSCPS10
BMXXTSCPS20
Any questions, feel free to contact us