Signal Conditioners and Modules
Pepperl+Fuchs KFU8-GUT-1.D Temperature Converter with Trip Values

Pepperl+Fuchs KFU8-GUT-1.D Temperature Converter with Trip Values

Model: KFU8-GUT-1.D

Supplier: Pepperl+Fuchs

Categories: Signal Conditioners and Modules

After sales service. If you have any questions, click here.

PRODUCT DESCRIPTION

Pepperl+Fuchs KFU8-GUT-1.D Temperature Converter with Trip Values

Transmitter Power Supply

General specifications

Signal type Analog input

Functional safety related parameters

Safety Integrity Level (SIL) SIL 2

Supply

Connection terminals 23, 24

Rated voltage 20 ... 90 V DC / 48 ... 253 V AC

Power dissipation/power consumption ≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA

Interface

Programming interface programming socket

Input

Connection side field side

Connection terminals 1, 2, 3, 4, 6

RTD Pt100, Pt500, Pt1000, Ni100, Ni1000

Measuring current approx. 400 µA

Types of measuring 2-, 3-, 4-wire technology

Lead resistance max. 50 Ω

Measurement loop monitoring sensor breakage, sensor short-circuit

Thermocouples type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995)

Cold junction compensation external and internal

Measurement loop monitoring sensor breakage

Potentiometer 0.8 ... 20 kΩ

Types of measuring 2-, 3-, 5-wire technology

Voltage 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV

Open loop voltage max. 5 V with resistance measuring sensor

Input resistance ≥ 250 kΩ (0 ... 10 V)

min. 1 MΩ (0 ... 1 V, -100 ... 100 mV)

Output

Connection side control side

Connection output I: terminals 10, 11, 12

output II: terminals 16, 17, 18

output III: terminals 8+, 7-

Output I, II relay

Contact loading 250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A

Mechanical life 5 x 107 switching cycles

Energized/De-energized delay approx. 20 ms / approx. 20 ms

Output III Analog current output

Current range 0 ... 20 mA or 4 ... 20 mA

Open loop voltage max. 24 V DC

Load max. 650 Ω

Fault signal downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43)

Transfer characteristics

Deviation

Temperature effect Input: 0.005 %/K (50 ppm) of span ; current output: 0.005 %/K (50 ppm) of span

RTD max. 0.2 % of span

Thermocouples max. 10µV

deviation of CJC: ±0.8 K

Voltage 0.1 % of span

Potentiometer 0.1 % of span when < 5 kΩ

0.5 % of span when > 5 kΩ

Current output max. 20 µA

Sampling rate approx. 700 ms

Galvanic isolation

Input/Other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output I, II against eachother reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output I, II/other circuits reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output III/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Interface/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Indicators/settings

Display elements LEDs , display

Control elements Control panel

Configuration via operating buttons

via PACTware

Labeling space for labeling at the front

Directive conformity

Electromagnetic compatibility

Directive 2014/30/EU EN 61326-1:2013 (industrial locations)

Low voltage

Directive 2014/35/EU EN 61010-1:2010

Conformity

Electromagnetic compatibility NE 21:2007

Degree of protection IEC 60529:2001

Ambient conditions

Ambient temperature -20 ... 60 °C (-4 ... 140 °F)

Mechanical specifications

Degree of protection IP20

Connection screw terminals

Mass 300 g

Dimensions 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2

Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001


Similar model numbers:

KFD2-CRG2-1.D

KFD2-GS-1.2W

KFD2-GUT-1.D

KFD2-USC-1.D

KFU8-CRG2-1.D

KFU8-GUT-1.D

KFU8-USC-1.D

KFD2-WAC2-1.D


Any questions, feel free to contact us

jeff@hkxytech.com   jeff@whxyauto.com   +86-15072331761

Related Products

Payment Methods