Pepperl+Fuchs KFD0-CC-1 Current/Voltage Converter
General specifications
Signal type Analog input
Supply
Rated voltage 12 ... 35 V DC loop powered
Power dissipation 0.4 W
Input
Connection side field side
Connection terminals 1+, 2-
Current range 0 ... 20 mA , load ≤ 50 Ω
Voltage range 0 ... 10 V , load ≥ 100 kΩ
Output
Connection side control side
Connection terminals 9+, 8-
Load (U -12 V) / 0.02 A
Current output 4 ... 20 mA , limited to ≤ 35 mA
Fault signal downscaling ≤ 3 mA
Transfer characteristics
Deviation
After calibration 0.1 % of full-scale value
Temperature effect span: 0.050 % of span /K ; zero point: 0.060 % of span /K
Linearization ≤ 0.04 % of full-scale value
Influence of supply voltage 6.5 ppm/V
Rise time 250 ms
Galvanic isolation
Input/Output safe isolation according to EN 50178, rated insulation voltage 253 Veff
Indicators/settings
Control elements DIP switch
potentiometer
Configuration via DIP switches
via potentiometer
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Insulation coordination EN 50178
Galvanic isolation EN 50178
Degree of protection IEC 60529
Ambient conditions
Ambient temperature -20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Similar model numbers:
KCD2-UT2-1
KFD0-CC-1
KFD0-TR-1
KFD2-GUT-1.D
KFD2-USC-1.D
KFD2-UT2-1
KFD2-UT2-2
KFU8-GUT-1.D
KFU8-USC-1.D
KFU8-VCR-1
KCD2-UT2-1
KFD2-UT2-1
KFD2-UT2-2
KFD2-WAC2-1.D
KFD0-TT-1
KFD2-UT2-1-1
KFD2-UT2-2-1