Pepperl+Fuchs KCD2-STC-1.SP SMART Transmitter Power Supply
General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection Power Rail or terminals 9+, 10-
Rated voltage 19 ... 30 V DC
Ripple ≤ 10 %
Rated current ≤ 45 mA at 24 V and 20 mA source mode output
Power dissipation ≤ 800 mW
Power consumption ≤ 1.1 W
Input
Connection side field side
Connection terminals 1+, 2-; 3+, 4-
Input signal 4 ... 20 mA limited to approx. 26 mA
Open circuit voltage/short-circuit current terminals 1+, 2-: 20 V / 26 mA
Voltage drop terminals 3+, 4- : approx. 5 V
Available voltage terminals 1+, 2-: ≥ 16 V at 20 mA ; ≥ 17 V at 4 mA
Output
Connection side control side
Connection terminals 5-, 6+
terminals 5-, 8+ for HART resistor
Load 0 ... 525 Ω (10.5 Vmax source mode)
Output signal source mode: 4 ... 20 mA or 1 ... 5 V (internal resistor: 250 Ω, 0.1 %)
sink mode: 4 ... 20 mA, operating voltage 5 ... 30 V
For additional internal or external loads (e. g. terminal +8) the voltage drop has to be considered, e. g. 250 Ω x 20 mA = 5 V.
Ripple 20 mV rms
Transfer characteristics
Deviation at 20 °C (68 °F)
< 0.1 % of full scale, incl. non-linearity and hysteresis (source mode and sink mode 4 ... 20 mA)
≤ ± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)
Influence of ambient temperature < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)) (source mode and sink mode 4 ... 20mA)
< 0.5 mV/K (-20 ... 70 °C (-4 ... 158 °F)); < 1 mV/K (-40 ... -20 °C (-40 ... -4 °F)) (source mode 1...5 V)
Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Settling time ≤ 50 ms
Rise time/fall time ≤ 10 ms
Galvanic isolation
Input/Output basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements LED
Control elements DIP switch
Configuration via DIP switches
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2017
EN 61326-3-2:2018
Degree of protection IEC 60529:2001
Ambient conditions
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection spring terminals
Mass approx. 100 g
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Similar model numbers:
KFD2-DWB-1.D
KFD2-SR2-2.W.SM
KFD2-UFC-1.D
KFD2-UFT-2.D
KFU8-DW-1.D
KFU8-DWB-1.D
KFU8-UFC-1.D
KFU8-UFT-2.D
KFU8-UFC-1.D.FA