Signal Conditioners and Modules
Pepperl+Fuchs KCD2-STC-1.2O SMART Transmitter Power Supply

Pepperl+Fuchs KCD2-STC-1.2O SMART Transmitter Power Supply

Model: KCD2-STC-1.2O

Supplier: Pepperl+Fuchs

Categories: Signal Conditioners and Modules

After sales service. If you have any questions, click here.

PRODUCT DESCRIPTION

Pepperl+Fuchs KCD2-STC-1.2O SMART Transmitter Power Supply

SMART Transmitter Power Supply

General specifications

Signal type Analog input

Functional safety related parameters

Safety Integrity Level (SIL) SIL 2

Systematic capability (SC) SC 3

Supply

Connection Power Rail or terminals 9+, 10-

Rated voltage 19 ... 30 V DC

Ripple within the supply tolerance

Power dissipation approx. 1.4 W at 20 mA transfer current, 250 Ω in both outputs

Power consumption 2 W

Input

Connection side field side

Connection terminals 1+, 2- (sink); 3+, 4- (source)

Input signal 0/4 ... 20 mA

Voltage drop terminals 3, 4: ≤ 6.1 V at 20 mA

Short-circuit current terminals 1+, 2-: 25 mA

Input resistance terminals 1+, 2-: max. 500 Ω (BRAIN)

(250 Ω load)

Available voltage terminals 1+, 2-: ≥ 16 V at 20 mA , ≥ 18.5 V at 4 mA

Output

Connection side control side

Connection source: terminals 5-, 6+; 7-, 8+

sink: terminals 5+, 6-, 7+, 8-

Load channel 1: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)

channel 2: 0 ... 500 Ω (20 mA)/> 1 MΩ (5 V)

Output signal 0/4 ... 20 mA or 0/1 ... 5 V

Ripple max. 50 µA rms

Transfer characteristics

Deviation Iout < 20 µA (0.1 %); Vout < 7.5 mV (0.15 %) incl. calibration, linearity, hysteresis and fluctuation of supply voltage, at 20 °C (68 °F), 0/4 ... 20 mA, 0/1 ... 5 V

Influence of ambient temperature current output: 0.25 µA/K

voltage output: 80 µV/K

Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)

control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB)

Settling time 6 ms

Rise time/fall time 2 ms

Galvanic isolation

Input/Output basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff

Input/power supply basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff

Output/power supply functional insulation, rated insulation voltage 50 V AC

Output/Output functional insulation, rated insulation voltage 50 V AC

Indicators/settings

Display elements LED

Control elements DIP switch

Configuration via DIP switches

Labeling space for labeling at the front

Directive conformity

Electromagnetic compatibility

Directive 2014/30/EU EN 61326-1:2013 (industrial locations)

Conformity

Electromagnetic compatibility NE 21:2012

EN 61326-3-2:2008

Degree of protection IEC 60529:2001

Protection against electrical shock UL 61010-1:2012

Ambient conditions

Ambient temperature -20 ... 60 °C (-4 ... 140 °F)

extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions

Mechanical specifications

Degree of protection IP20

Connection screw terminals

Mass approx. 100 g

Dimensions 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2

Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001


Similar model numbers:

KCD2-STC-1.2O

KFD2-CRG2-1.D

KFD2-STC5-1

KFD2-STC5-1.2O

KFD2-STC5-2

KFU8-CRG2-1.D

KFU8-VCR-1

KCD2-STC-1

KCD2-STC-1.SP


Any questions, feel free to contact us

jeff@hkxytech.com   jeff@whxyauto.com   +86-15072331761

Related Products

Payment Methods