Signal Conditioners and Modules

PRODUCT DESCRIPTION

Pepperl+Fuchs KFD0-RSH-1 Relay Module

Relay Module2

General specifications

Signal type Digital Output

Functional safety related parameters

Safety Integrity Level (SIL) SIL 3

Supply

Rated voltage loop powered

Power dissipation < 1.5 W

Power consumption < 1.5 W

Input

Connection side control side

Connection terminals 7, 8

Pulse/Pause ratio min. 20 ms / min. 20 ms

Signal level 0-signal: 0 ... 5 V DC

1-signal: 16 ... 30 V

Rated current approx. 50 mA

Output

Connection side field side

Connection terminals 2, 3

Contact loading 230 V AC/2 A/cos φ 0.7; 40 V DC/2 A resistive load

Minimum switch current 2 mA / 24 V DC

Energized/De-energized delay approx. 10 ms / approx. 5 ms

Mechanical life 5 x 106 switching cycles

Electrical life 2 x 105 switching cycles , at maximum load

Fuse rating 2.5 A

recommended maximum utilization of the fuse: 80 %

Transfer characteristics

Switching frequency < 10 Hz

Galvanic isolation

Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Indicators/settings

Display elements LED

Labeling space for labeling at the front

Directive conformity

Electromagnetic compatibility

Directive 2014/30/EU EN 61326-1:2013 (industrial locations)

Low voltage

Directive 2014/35/EU EN 61010-1:2010

Conformity

Electromagnetic compatibility NE 21:2006

Degree of protection IEC 60529:2001

Ambient conditions

Ambient temperature -20 ... 60 °C (-4 ... 140 °F)

Mechanical specifications

Degree of protection IP20

Connection screw terminals

Mass approx. 100 g

Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2

Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001


Similar model numbers:

KFD2-DWB-1.D

KFD2-SR2-2.W.SM

KFD2-UFC-1.D

KFD2-UFT-2.D

KFU8-DW-1.D

KFU8-DWB-1.D

KFU8-UFC-1.D

KFU8-UFT-2.D

KFU8-UFC-1.D.FA