Pepperl+Fuchs KFD2-SR2-2.W.SM Standstill and Rotational Direction Monitor

Switch Amplifier3

General specifications

Signal type Digital Input

Programming via DIP switch and programmable

Functional safety related parameters

Safety Integrity Level (SIL) SIL 2

Supply

Connection terminals 14+, 15-

Rated voltage 20 ... 30 V DC

Power consumption max. 1.5 W

Input

Connection side field side

Connection Input I: terminals 1+, 2+, 3- ;

Input II: terminals 4+, 5+, 6-

Rated values acc. to EN 60947-5-6 (NAMUR)

Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA

Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA

Line fault detection not available

Control input sensor power supply approx. 8.2 V, impedance 1.2 kΩ

Pulse duration > 200 µs for standstill monitoring,

> 250 µs for rotation direction detecion

Output

Connection side control side

Connection output I: terminals 7, 8, 9 ;

output II: terminals 10, 11, 12

Contact loading 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load

Minimum switch current 2 mA / 24 V DC

Energized/De-energized delay approx. 20 ms / approx. 20 ms

Mechanical life 107 switching cycles

Trip value for standstill monitoring:

0.1 Hz; 0.5 Hz; 2 Hz; 10 Hz

adjustable via DIP switch (S1 and S2)

Transfer characteristics

Accuracy 5 % (S3 = I), 30 % (S3 = II)

Start-up override 5 seconds or 20 seconds, programmable

Frequency range ≤ 2 kHz

Rotation direction detection 90° phase difference between pulse input signal 1 and 2, overlapping ≥ 125 µs

Galvanic isolation

Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Output/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff

Indicators/settings

Display elements LEDs

Control elements DIP switch

Configuration via DIP switches

Labeling space for labeling at the front

Directive conformity

Electromagnetic compatibility

Directive 2014/30/EU EN 61326-1:2013 (industrial locations)

Low voltage

Directive 2014/35/EU EN 61010-1:2010

Conformity

Electromagnetic compatibility NE 21:2006

Degree of protection IEC 60529:2001

Input EN 60947-5-6:2000

Ambient conditions

Ambient temperature -20 ... 60 °C (-4 ... 140 °F)

Mechanical specifications

Degree of protection IP20

Connection screw terminals

Mass approx. 150 g

Dimensions 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2

Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001


Similar model numbers:

KFD2-DWB-1.D

KFD2-SR2-2.W.SM

KFD2-UFC-1.D

KFD2-UFT-2.D

KFU8-DW-1.D

KFU8-DWB-1.D

KFU8-UFC-1.D

KFU8-UFT-2.D

KFU8-UFC-1.D.FA


Any questions, feel free to contact us

jeff@hkxytech.com   jeff@whxyauto.com   +86-15072331761

Related Products

Payment Methods