Pepperl+Fuchs KCD2-SR-1.LB Switch Amplifier
General specifications
Signal type Digital Input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection Power Rail or terminals 9+, 10-
Rated voltage 19 ... 30 V DC
Ripple ≤ 10 %
Rated current ≤ 37 mA
Power dissipation ≤ 750 mW
Power consumption ≤ 750 mW
Input
Connection side field side
Connection terminals 1+, 2-
Rated values acc. to EN 60947-5-6 (NAMUR)
Open circuit voltage/short-circuit current approx. 8 V DC / approx. 8 mA
Switching point/switching hysteresis 1.2 ... 2.1 mA / approx. 0.2 mA
Line fault detection breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA
Pulse/Pause ratio min. 20 ms / min. 20 ms
Output
Connection side control side
Connection output I: terminals 5, 6 ; output II: terminals 7, 8
Output I signal ; relay
Output II signal or fault message ; relay
Contact loading 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load
Minimum switch current 2 mA / 24 V DC
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Mechanical life 107 switching cycles
Transfer characteristics
Switching frequency ≤ 10 Hz
Galvanic isolation
Input/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/Output reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements LEDs
Control elements DIP switch
Configuration via DIP switches
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EU EN 61010-1:2010+A1:2019+A1:2019/AC:2019
Conformity
Electromagnetic compatibility NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018
Degree of protection IEC 60529:1989+A1:1999+A2:2013
Functional safety IEC/EN 61508:2010
Input EN 60947-5-6:2000
Ambient conditions
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Similar model numbers:
KCD2-SOT-1.LB
KCD2-SOT-2
KFA6-ER-1.6
KFA6-ER-1.W.LB
KFA6-SR-2.3L
KFA6-SR-2.3L.FA
KFD2-ER-1.W.LB
KFD2-SR3-2.2S
KFU8-SR-1.3L.V
KFD2-ER-1.6
KCD2-SR-1
KCD2-SR-1.LB
KCD2-SR-2
KCD2-SOT-1.LB.SP
KCD2-SOT-2.SP
KCD2-SR-1.LB.SP
KCD2-SR-2.SP
KCD2-ST-1.LB
KCD2-ST-1.LB.SP
KCD2-ST-2
KCD2-ST-2.SP
KFA5-ER-1.W.LB
KFA6-ER-1.5
KFA6-ER-2.W.LB
KFD2-ER-2.W.LB
KFD2-SR2-2.2S
KFD2-ER-1.5
Any questions, feel free to contact us
jeff@hkxytech.com jeff@whxyauto.com +86-15072331761