Pepperl+Fuchs KFD2-PT2-Ex1-1 Potentiometer Converter
General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Supply
Connection Power Rail or terminals 11+, 12-
Rated voltage 20 ... 35 V DC
Ripple within the supply tolerance
Power dissipation 0.5 W
Power consumption 0.6 W
Input
Connection side field side
Connection terminals 4-, 5-, 3+, 2+, 1+
Potentiometer
Types of measuring 3-, 4-, 5-wire technology
Nominal resistance 800 Ω to 100 kΩ
Supply voltage approx. 4.7 V
Lead resistance 5 % of the potentiometer resistance (adjustable)
Output
Connection side control side
Connection terminals 7-, 8+
Voltage output 0 ... 5 V
Output resistance max. 30 Ω
Transfer characteristics
Accuracy 0.05 %
Deviation
Linearity ≤ ± 5 mV
Influence of ambient temperature ≤ 0.5 mV/K
Rise time 10 to 90 % ≤ 8 ms; 10 to 90 % within 1 % of span ≤ 25 ms
Galvanic isolation
Output/power supply functional insulation, rated insulation voltage 50 V AC
Indicators/settings
Control elements potentiometer
Configuration via potentiometer
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2006
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 120 g
Dimensions 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Similar model numbers:
KCD2-UT2-Ex1
KFD0-CC-Ex1
KFD0-TR-Ex1
KFD0-TT-Ex1
KFD2-GUT-Ex1.D
KFD2-PT2-Ex1
KFD2-PT2-Ex1-5
KFD2-UT2-Ex1
KFD2-UT2-Ex1-1
KFD2-UT2-Ex2
KFU8-GUT-Ex1.D
KFD2-WAC2-Ex1.D
KFD2-PT2-Ex1-1
KFD2-PT2-Ex1-4
KFD2-PT2-Ex1-6-Y112844
KFD2-PT2-Ex1-Y98312
KFD2-UT2-Ex2-1
KFD2-WAC2-Ex1.D-Y1
Any questions, feel free to contact us
jeff@hkxytech.com jeff@whxyauto.com +86-15072331761