Intrinsic Safety Barriers
Pepperl+Fuchs KFD2-HLC-Ex1.D HART Loop Converter

Pepperl+Fuchs KFD2-HLC-Ex1.D HART Loop Converter

Model: KFD2-HLC-Ex1.D

Supplier: Pepperl+Fuchs

Categories: Intrinsic Safety Barriers

After sales service. If you have any questions, click here.

PRODUCT DESCRIPTION

Pepperl+Fuchs KFD2-HLC-Ex1.D HART Loop Converter

Switch Amplifier9


General specifications

Signal typeAnalog input

Supply

ConnectionPower Rail or terminals 23+, 24-

Rated voltage19 ... 30 V DC

Rated currentapprox. 120 mA at 24 V DC

Power dissipation2.3 W

Power consumption2.9 W

HART signal channels (intrinsically safe)

ConformityHART field device input (revision 5 to 7)

Interface

Programming interfaceprogramming socket

Input

Connection sidefield side

Connectionterminals 1, 2, 3, 4, 5, 6

Open circuit voltage/short-circuit currenttyp. 24 V / 28 mA

Input resistance250 Ω , 5 % (terminals 2, 3 and with jumper on 5, 6)

Available voltage≥ 15.5 V at 20 mA, short-circuit protected

Output

Connection sidecontrol side

Connectionoutput I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21

Output signalanalog

Voltage range5 ... 30 V , sink mode from external supply

Current range4 ... 20 mA , (source or sink mode)

Loadmax. 650 Ω , source mode

Fault signaldownscale I ≤ 2 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) or hold measurement value

Other outputsHART communicator on terminals 22, 24

Collective error messagePower Rail and LED red

Transfer characteristics

Output I, II, III

Resolutionmax. 2 µA

Accuracy< 20 µA, 10 µA typ.

Influence of ambient temperature< ± 2 µA/K

Duration of measurement/Response delayHART message acquisition time plus 100 ms

Galvanic isolation

Output I/II/III/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff

Indicators/settings

Display elementsLEDs , display

Control elementsControl panel

Configurationvia operating buttons

via PACTware

Labelingspace for labeling at the front

Directive conformity

Electromagnetic compatibility

Directive 2014/30/EUEN 61326-1:2013 (industrial locations)

Low voltage

Directive 2014/35/EUEN 61010-1:2010

Conformity

Electromagnetic compatibilityNE 21:2006

Degree of protectionIEC 60529:2001

Ambient conditions

Ambient temperature-20 ... 60 °C (-4 ... 140 °F)

Mechanical specifications

Degree of protectionIP20

Connectionscrew terminals

Mass300 g

Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2

Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001


Similar model numbers:

KCD2-STC-Ex1.2O

KCD2-STC-Ex1.2O.ES

KCD2-STC-Ex1.ES

KFD2-CRG2-Ex1.D

KFD2-HLC-Ex1.D

KFD2-HLC-Ex1.D.2W

KFD2-STC5-Ex1

KFD2-STC5-Ex1.2O

KFD2-STC5-Ex1.2O.H

KFD2-STC5-Ex1.H

KFD2-STC5-Ex2

KFU8-CRG2-Ex1.D

KCD2-STC-Ex1-Y1

KCD2-STC-Ex1.ES.SP

KFD2-STC4-Ex1.2O-Y1

KFD2-STC4-Ex2-Y1

KCD2-STC-Ex1.2O.DE

KFD2-HLC-Ex1.D.4S

KCD2-STC-Ex1

KCD2-STC-Ex1.SP

KFD2-STC4-Ex1

KFD2-STC4-Ex1-Y1

KFD2-STC4-Ex1.2O

KFD2-STC4-Ex1.H

KFD2-STC4-Ex2

KFD2-STC4-Ex1.2O.H

KFD2-STV4-Ex1-1

KFD2-STV4-Ex1-2

KFD2-STV4-Ex1.2O-1

KFD2-STV4-Ex1.2O-2

KFD2-STV4-Ex2-1

KFD2-STV4-Ex2-2

KFD2-STV5-Ex1-1


Any questions, feel free to contact us