Pepperl+Fuchs KCD2-SLD-Ex1.1065 Solenoid Driver
General specifications
Signal type Digital Output
Functional safety related parameters
Safety Integrity Level (SIL) SIL 3
Systematic capability (SC) SC 3
Supply
Connection terminals 5+, 6- loop powered
Power Rail or terminals 9+, 10- bus powered
Rated voltage 19 ... 30 V DC
loop powered
Input current 80 mA at 24 V
Power dissipation 1.3 W at 24 V
Load 150 Ω
Input
Connection side control side
Connection terminals 5+, 6-
Test pulse length max. 2 ms from DO card
Signal level loop powered
1-signal: 19 ... 30 V DC
0-signal: 0 ... 5 V DC
bus powered
1-signal: 15 ... 30 V DC (current limited at 5 mA)
0-signal: 0 ... 5 V DC
Rated current 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card)
1-signal: ≥ 36 mA (minimum load current DO card)
Inrush current < 200 mA , 10 ms loop powered
Output
Connection side field side
Connection terminals 1+, 2-
Internal resistor 80 Ω
Current typ. 65 mA
Voltage typ. 10 V
Current limit 65 mA
Open loop voltage typ. 16.4 V
Load nominal 0.05 ... 18 kΩ
Output II fault signal
Connection terminals 7, 8 , non-intrinsically safe
Contact loading 30 V DC/ 0.5 A resistive load
Mechanical life 105 switching cycles
Energized/De-energized delay ≤ 20 ms / ≤ 20 ms
Line fault detection signal at short-circuit Rload < 25 Ω, lead breakage Rload > 50 kΩ ; test current < 500 µA
Galvanic isolation
Output/other circuits basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output II/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff
Indicators/settings
Display elements LEDs
Control elements DIP switch
Configuration via DIP switches
Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2012 , EN 61326-3-2:2008
For further information see system description.
Degree of protection IEC 60529:2013
Protection against electrical shock EN 61010-1:2010
Ambient conditions
Ambient temperature -20 ... 60 °C (-4 ... 140 °F)
Observe the temperature range limited by derating, see section derating.
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 150 g
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Similar model numbers:
KCD0-SD3-Ex1.1045
KCD0-SD3-Ex1.1245
KCD2-SLD-Ex1.1045
KCD2-SLD-Ex1.1065
KCD2-SLD-Ex1.1245
KFD0-SD2-Ex1.10100
KFD0-SD2-Ex1.1180
KFD2-VM-Ex1.35.L
KFD2-SLD-Ex1.13100
KCD0-SD3-Ex1.1245.SP
KCD0-SD-Ex1.1245
KCD0-SD-Ex1.1245.SP
KFD0-SD2-Ex1.1045
KFD0-SD2-Ex1.1065
KFD0-SD2-Ex2.1045
KFD0-SD2-Ex2.1245
KFD2-SL2-Ex2
KFD2-SL2-Ex2.B
Any questions, feel free to contact us